INTRODUCTION
The
location chosen for the water heater must take into consideration
the following:
LOCAL
INSTALLATION REGULATIONS:
This
water heater must be installed in accordance with these instructions,
local codes, utility company requirements, and/or in the absence
of local codes, the latest edition of the American National Standard,
National Fuel Gas Code. A copy can be purchased from either American
Gas Association, 1515 Wilson Blvd., Arlington, VA 22209 as booklet
Z223.1 or National Fire Prevention Association, Batterymarch Park,
Quincy, MA 02269 as booklet NFPA No. 54.
LOCATION:
1.
A gas fired water heater should not be installed in a space where
liquids which give off flammable vapors are to be used or stored.
Such liquids include gasoline, L.P. Gas (butane and propane), paint
and adhesives and their thinners, solvents or removers. Because
of natural air movement in a room or other enclosed space, flammable
vapors can be carried some distance from where their liquids are
being used or stored. The open flame of the water heater’s pilot
light or main burner can ignite these vapors causing an explosion
or fire which may result in severe burns or death to those in range,
as well as property damage.
For
these reasons installation of a gas fired water heater in a garage
is not desirable.
If
a location in the garage is the only alternative, the gas fired
water heater should be installed so that the open flame of the pilot
and main burner are no less than 40 inches above the garage floor.
Raising
the gas fired water heater will reduce BUT NOT eliminate the possibility
of lighting the vapors of any flammable liquids which may be improperly
stored or accidentally spilled.
2.
The water heater should be installed as close as practical to the
gas vent or chimney. Long hot water lines should be insulated to
conserve water and energy.
The water heater and water lines should be protected from freezing
temperatures. DO NOT the water heater in bathrooms, any occupied
rooms normally kept closed nor in outdoor unprotected areas.
3. The water heater must be installed with the minimum clearances
to combustible material of 6 inches at the sides, 2 inches at the
rear and 16 inches above the top of the draft hood outlet. For alcove
installation, the water heater shall be installed above noncombustible
flooring.
NOTE:
A minimum of 24 inches clearance from front should be available
for adequate inspection and servicing.
4. CAUTION! The water heater should not be located in an area
where leakage of the water heater will result in damage to the area
adjacent to it or to lower floors of the structure. When such areas
cannot be avoided, it is recommended that a suitable catch pan,
adequately drained, be installed below the water heater. The pan
MUST NOT restrict combustion air flow.
NOTE:
Auxiliary catch pan installation MUST conform to local codes.
5.
COMBUSTION & VENTILATION AIR:
Proper
operation of the water heater requires air for combustion and ventilation.
If the water heater is installed in an unconfined space within a
building of conventional frame, masonry or metal construction, infiltration
air is normally adequate for proper combustion and ventilation.
The
confined space should be provided with 2 permanent openings: one
commencing within 12 inches of the top and one commencing within
12 inches of the bottom. Each opening should have a total
free area of not less than that as follows depending upon the type
of installation.
(a) If all air for combustion comes from inside the buildings:
Each opening should have a minimum free area of 1 square inch per
1,000 Btu per hour of the total input rating of all gas utilization
equipment in the confined space, but not less than 100 square inches.
(b) If all air for combustion comes from outdoors:
I. When directly communicating with the outdoors
and communicating with the outdoors through vertical ducts, each
opening should have a minimum free area of 1 square inch per 4,000
Btu per hour of total input rating of all equipment in the enclosure.
II. When communicating with the outdoors through
horizontal ducts, each opening should have a minimum free area of
1 square inch per 2,000 Btu per hour of total input rating of all
equipment in the enclosure.
III. When ducts are used, they should be of the same
cross-sectional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts should not
be less than 3 inches.
NOTE:
In calculating free area, consideration should be given to the
blocking effect of louvers, grills or screens protecting openings.
Protective
screening for the openings MUST NOT be smaller than 1/4 inch mesh
to resist clogging by lint or debris.
Provisions
for combustion and ventilation air must comply with the referenced
codes and standards.
See Regulation Section.
6.
CORROSIVE ATMOSPHERE:
The
water heater should not be installed near an air supply containing
halogenated hydrocarbons. For example, the air in beauty shops,
dry cleaning establishments, photo processing labs, and storage
areas for liquid and powdered bleaches or swimpool chemicals often
contain such hydrocarbons. The air there may be safe to breathe,
but when it passes through a gas flame, corrosive elements are released
that will shorten the life of any gas burning appliance. Propellants
from common spray cans or gas leaks from refrigeration equipment
are highly corrosive after passing through a flame.
7.
PROHIBITED INSTALLATIONS:
WARNING!!
DO NOT INSTALL THE WATER HEATER IN THE FOLLOWING LOCATIONS:
a. In small, poorly ventilated rooms.
b. In airtight rooms with air-conditioning.
c. Near vents for heating or cooling.
d. In places where chemicals are used.
e. In bathrooms, bedrooms or any occupied rooms normally
kept closed.
f. In a location where a water heater may be exposed to
freezing temperatures.
g. In a location where the water heater is subject to vibration.
(such as Carpet Cleaning, etc.)
h. In Recreational Vehicles, Mobile Homes, Boats and other
water crafts.
i. As a part of any circulating systems (such as Home Heating,
Spa or Pool Heating, Re-Circulation to the other tank, etc.)
j. In corrosive, dusty and greasy environments.
8. METHOD OF INSTALLATION:
|
A.
For PH-6 series
The
bracket attached on the water heater should be secured on
a wooden post or wall by means of a total of 3 wood screws.
DO NOT use nails.
A top screw should be fixed with a clearance of 1/8 inch between
wall and screw head where the water heater bracket is hung
up. Water heater should be secured with two bottom screws.
B.
For PH-12M & 24M series
a.
The bracket may be secured to a wooden post or bar by means
of a total of 6 wood screws. DO NOT use nails.
b. When the bracket is to be mounted on a concrete wall
or a rigid wooden post, it may be attached securely in position
by use of a pair of dry pit 3/8 or coach screws (3/8) passed
through the upper and the lower oval slot in the bracket.
|
 |
NOTE:
Any local ordinances and regulations relating to the installation
of the water heater should be strictly observed.
NOTE:
The water heater which will be used to supply potable water shall
not be connected to any heating system or component(s) previously
used with a nonpotable water heating appliance.
INSTALLATIONS
NOTE:
INSTALLATIONS (PLUMBING, ETC.) SHOULD BE DONE BY A CERTIFIED
AND/OR LICENSED PLUMBER. ALL MODELS SHALL BE INSTALLED INDOORS
AT VERTICAL POSITION ON A WALL.
1.
INSPECT SHIPMENT:
Inspect water heater for possible damage. Check the marking of the
rating plate of the water heater to be certain the type of gas being
furnished corresponds to that for which the water heater is equipped.
2.
WATER SUPPLY CONNECTIONS:
a.
The water supply to the water heater should be such as to provide
sufficient pressure to properly operate the water actuated control
valve. The minimum working water supply pressure is shown
in the table. However, additional supply pressure is required above
the minimum pressure to cover any pressure head loss or drop in
hot water supply lines. Make sure that the total water pressure
at the inlet is sufficient to operate water heater at full capacity.
|
Models
|
Minimum
water supply pressure
|
| PH-6
series |
4.3
P.S.I.
|
| PH-12M
series |
2.1
P.S.I.
|
| PH-24M
series |
2.4
P.S.I.
|
b.
Install a shutoff valve near the water inlet of the water heater
for purpose of the servicing and draining.
c.
Connection between the water heater and places where hot water is
used should be as short and direct as possible, and a uniform pipe
size of sufficient diameter to carry the full capacity of hot water
should be used.
d.
Be sure to connect the water inlet and the hot water outlet as shown
on the water heater. If reversed, the water heater will not function.
NOTE:
Make sure the water filter is in the water inlet connection.
e.
When hot water flows through the supply line there is an invisible
heat loss, regardless of type of water heater. Thus, insulation
or protection of hot water piping is encouraged.
NOTE:
For PH-6 series, well water systems should be set at a range
of 40-60 P.S.I.
NOTE:
Some model may require to remove all restrictions from faucets
& shower heads.
3.
RELIEF VALVE:
A
new combination pressure and temperature relief valve, complying
with the Relief Valve Standard, ANSI Z21.22-1986, must be installed
at the hot water outlet connection of the water heater at the time
of installation. Local codes should govern the installation of the
relief devices.
For
safe operation of the water heater, be sure that:
(
I ) No valve is placed between the relief valve and the water heater.
( II ) Discharge from the relief device is conducted to a suitable
place for disposal when relief occurs.
( III ) No reducing coupling or other restrictions are installed
in discharge line, and
( IV ) Discharge line is installed to allow complete drainage of
the device and line.
( V ) The pressure rating of the relief valve must not exceed 150
P.S.I., the maximum working pressure of the water heater as marked
on the rating plate.
( VI ) The BTUH rating of the relief valve must equal or exceed
the BTUH input of the water heater as marked on its rating plate.
( VII ) The end of the discharge line should not be threaded or
concealed and should be protected from freezing.
NOTE:
Manual operation of the pressure-temperature relief valves
should be done at least once a year. Turn off the gas intake valve,
open the hot water tap and then check the operation of safety
relief valve. You should take precautions to avoid contact with
hot water coming out of relief valve and to prevent water damage.
NOTE:
If the temperature and pressure relief valve on the system discharges
periodically, a problem exists and service to the water system
is required.
CAUTIONS!!
This water heater must only be used with the following water
supply system conditions:
a. With clean, potable water (drinkable and harmless to
mankind) free of corrosive chemicals, sand, dirt, hair or other
contaminants.
b. With inlet water temperatures above 32 degrees F, but not exceeding
90 degrees F.
c. In non-circulating systems.
d. With the heat exchanger free of lime and scale deposits.
4.
GAS SUPPLY CONNECTION:
a.
The gas supply lines should be gas-tight and of such size, and so
installed, as to provide a supply of gas sufficient to meet the
maximum demand of the water heater without undue loss of pressure.
b. ANSI approved steel or wrought-iron pipe should be used for gas
piping.
c. A metal-to-metal type union and shutoff valve should be installed
between the water heater and the gas supply pipe. A pipe joint compound
resistant to the action of liquefied petroleum gas on the threaded
joints must be used.
d. The gas supply piping must include a drip leg in close proximity
to the water heater.
|
Type
of Gas
|
Maximum
supply pressure
|
| L.P.
Gas |
13"
W.C.
|
| Natural
Gas |
10.5"
W.C.
|
|
Models
|
Minimum
supply pressure
L.P. Gas
|
Minimum
supply pressure
Natural Gas
|
| PH-6
series |
10
|
3.9
|
| PH-12M
series |
11.1
|
4.7
|
| PH-24M
series |
11
|
4.7
|
f.
After the water heater is connected to the gas supply, all connections
including water heater must be checked for leakage with soapy water,
bubble solution or other acceptable means before placing the water
heater in operation. DO NOT use Matches, Candles or other sources
of ignition for the purpose of leakage test.
g.
The appliance must be isolated from the gas supply piping system
by closing its individual manual shutoff valve during and pressure
testing of the gas supply piping system at test pressures equal
to or less than 1/2 psig (3.5 kPa).
WARNING:
Install the gas pressure regulators, in the gas supply line, which
do not exceed the maximum supply pressure mentioned above. DO
NOT use the gas pressure regulators, such as the industrial gas
pressure regulators, as they are intended for use with medium
and high pressure gas. If the gas supply pressure exceeds the
maximum mentioned above, imperfect combustion may result and the
life of the water heater may be shortened.
MOREOVER,
EXCEEDING INDICATED MAXIMUM GAS PRESSURE MAY CAUSE SERIOUS DAMAGE
TO THE WATER HEATER AS WELL AS PERSONAL INJURY. MAKE SURE TO INSTALL
A PROPER GAS PRESSURE REGULATOR UNDER THE MAXIMUM SUPPLY PRESSURE
MENTIONED ABOVE. IF PRESSURE IS LOW, GAS MAY BE INSUFFICIENT TO
HEAT WATER.
5.
VENTING:
The
water heater should be connected to a gas venting system constructed
so as to adequately remove flue gases to the outside atmosphere.
a.
The vent connectors must be attached to the draft hood outlet to
connect the water heater to the gas vent or chimney. The vent connectors
must be the same size (diameter) as the draft hood outlet or larger,
never smaller. For proper venting in certain installations
a larger vent connector size may be needed. Consult Vent Tables
in Appendix "G" of the National Fuel Gas Code (ANSI Z223.1
of NFPA booklet 54).
|
Models
|
Flue
size (D)
|
| PH-6
series |
4"
diameter
|
| PH-12M
series |
5"
diameter
|
| PH-24M
series |
7"
diameter
|
b.
The terminal of the flue pipe should be extended at least 2 feet
above the highest point where it passes through a roof of a building
and at least 2 feet higher than any portion of a building within
a horizontal distance of 10 feet.
c.
Horizontal vent connectors must be pitched upward to the chimney
at least 1/4" per foot of length.
d.
Single wall vent connectors must be at least 6" from adjacent
unprotected combustible surfaces. Joint of vent connectors should
be securely fastened by sheet metal screws or other approved method.
e.
The location of the pipe passing through a wall should be protected
by noncombustible material to provide sufficient clearance from
the pipe.
f.
All portions of the pipe should be adequately supported for the
design and weight of the material employed.
g.
A cap or a roof assembly should have a venting not less than that
of the pipe to which it is attached.
h.
DO NOT install the flue outlet in a wind pressure drift area as
shown below.
A
venting system should be designed and constructed so as to develop
a positive flow adequate to remove flue gases to the outside atmosphere.
WARNING:
The manufacturer’s warranty does not cover any damage or defect
caused by installation, attachment or use of any type of energy
saving or other unapproved devices into, onto or in conjunction
with the water heater. The use of unauthorized energy saving devices
may shorten the life of the water heater and may endanger life
and property. The manufacturer disclaims any responsibility for
such loss injury resulting from the use of such unauthorized devices.
INSTALLATION
CHECK LIST
A.
Water Heater Location
 |
Close
to area of vent. |
|
 |
Indoors
and protected from freezing temperatures. |
|
 |
Proper
clearance from combustible surfaces observed. |
|
 |
Sufficient
fresh air supply for proper operation of water heater. |
|
 |
Air
supply free of corrosive elements and flammable vapors. |
|
 |
Provisions
made to protect area from water damage. |
|
 |
Sufficient
room to service heater. |
|
B.
Water Supply
 |
Water
filter is located in original position. |
 |
Water
passes through the water heater. |
 |
Water
heater and piping air vented. |
 |
Water
connections tight and free of leaks. |
C.
Relief Valve
 |
Temperature
and Pressure Relief Valve properly installed and discharge line
run to open drain. |
 |
Discharge
line protected from freezing. |
D.
Gas Supply
 |
Gas
line equipped with shut-off valve. Union and sediment trap/drip
leg. |
 |
Approved
pipe joint compound used. |
 |
Soap
and water solution used to check all connections and fittings
for possible gas leak. |
 |
Gas
company inspected installation (if required). |
E.
Venting
 |
Vent connector(s) pitched upward to chimney
(1/4" per foot of length minimum). |
 |
Vent connector(s) securely fastened together
with screws. |
 |
Single wall vent connector(s) at least 6"
from combustible material. |